Requirements for alarm acknowledgment
For automatic bi-directional alarm acknowledgment to function, there are specific conditions which must be met:
-
The CCure 9000 event must have triggered the alarm in XProtect.
-
Check the Access Control tab, and the Events list, in the Smart Client to view the event.
-
Verify the Access Control Event Category used in the Alarm Definition in XProtect Management Client matches the category assigned to the event in the Access Control Events list.
-
The source of the alarm must correspond to the source exposed by the integration. For some CCure 9000 events, a door will be used as the source. For other events, such as user-created events, theCCure 9000 server is exposed as the source. It is required to specify the source in the Alarm Definition in XProtect.
-
The source of each event is listed in the Access Control tab’s Event list in the Smart Client.
-
The CCure event must be configured to require acknowledgment and must not be in a state that prevents acknowledgment, such as Latched.
-
Verify individual event details in the Configuration menu of the Administration Station application for the CCure 9000 system.